Skip to content
Water and Plumbing

Thermal Power and Flow Calculation (Q = m · c · ΔT)

Thermal power ↔ flow rate conversion according to the supply–return temperature difference.

The heat carried in hot water and thermal oil installations is determined by the flow rate and the supply–return temperature difference. This tool calculates the thermal power from the flow rate or the required flow rate from the thermal power . The density and specific heat of the water are taken at average temperature with IAPWS-IF97; typical values for glycol and thermal oil are filled in, you can also enter your own values.

Formula

Q = ṁ · c · ΔT    ṁ = ρ · V̇

Example

For a thermal power of 1,000 kW, the flow required in a hot water circuit operating at 90/70 °C (ΔT = 20 K) is approximately 44.1 m³/h. A flow rate of 10 m³/h carries 227 kW of heat at 80/60 °C.

You can calculate the pipe diameter and pump power based on the selected flow rate. For thermal oil boilers, use the thermal oil option. You can consult Çiftel Kazan engineers for your boiler room and plumbing project.