The optimal water pipe diameter according to the speed and pressure loss limits.

This tool selects the smallest pipe diameter for the water flow rate you enter, which meets both the speed and pressure loss limits per meter . It can be used for heating, cooling, boiler feed and process water lines. The result table also shows the velocity and loss values of the neighboring diameters.

Recommended values

  • Heating/cooling distribution lines: 0.5–1.5 m/s, 100–150 Pa/m
  • Boiler room main headers: 1–2 m/s
  • Pump suction lines: 0.5–1 m/s (to prevent cavitation)

Example

For an EN 10255 pipe with a limit of 1.5 m/s and 150 Pa/m for 25 m³/h of water at 70 °C, the choice is DN100 (0.80 m/s, 55 Pa/m). For 100 m³/h, DN150 is selected for a DIN 2448 pipe (1.39 m/s, 96 Pa/m).

Use the thermal power and flow tool to find the required flow from the thermal power. You can consult Çiftel Kazan engineers for your boiler room and installation project.