As water evaporates in the steam boiler, dissolved solids (TDS) accumulate in the boiler water. To keep it within limits, some of the boiler water is regularly drained off; this is called blowdown. This tool calculates the required blowdown rate, blowdown flow rate, and blowdown heat loss.
Formula
Blowdown rate = Steam flow rate × F ÷ (B − F)
F: feed water TDS, B: allowable TDS (ppm) for boiler water. Heat loss is calculated from the difference in enthalpy of saturated water and make-up water at boiler pressure.
Example
If the feed water TDS is 150 ppm, the allowed boiler water TDS is 3,000 ppm and the steam flow rate is 5,000 kg/h, the blowdown rate is 5.26% and the blowdown flow rate is 263 kg/h.
For details about water treatment and blowdown, you can refer to our boiler water treatment article.