Skip to content
Compressed Air, Gas & Electric

Compensation (Power Factor Correction) Calculation

Capacitor power (kVAr) and current reduction required to correct cos φ.

Inductive loads (motors, transformers) draw reactive power from the grid as well as active power. Reactive power causes cable losses, takes up transformer capacity and reactive energy penalty when exceeding the limit. This tool calculates the capacitor power required to increase the power factor to the desired value.

Formula

Qc = P · (tan φ₁ − tan φ₂)

P: active power (kW), φ₁: existing, φ₂: target power factor angle.

Example

To increase the cos φ from 0.75 to 0.98 in a plant with an average load of 250 kW, approximately 170 kVAr of compensation is required. With this correction, the line current decreases from 481 A to 368 A, i.e. 23.5%, at 400 V.

The default target (0.98) in the tool is according to the reactive energy limit in Turkey. For facilities outside Turkey, the electricity distribution company determines the limit; in the target box, type the value desired by your own network.

In stepped automatic compensation panels, the total power is selected slightly larger than the calculated value and divided into stages. You can consult Çiftel Kazan engineers for your boiler room and installation project.

FAQ

Frequently Asked Questions

Chat on WhatsApp Get a Quote