The air entering the steam system (at first start-up, in vacuum zones or from the feed water) mixes with the steam. Even if the pressure of the mixture remains the same, the partial pressure of the steam decreases; the temperature also decreases to the saturation temperature at that partial pressure. In addition, the air forms an insulating film on the heating surface.
Formula (Dalton’s law)
Example
If 10% air by volume is mixed with 5 bar(g) of steam, the temperature will be 154.8 °C instead of 158.9 °C; that is, it drops by 4.1 °C . If 150 °C is measured at the same pressure, there is approximately 21% air in the steam.
Thermostatic air vents are placed at the ends of the lines and the upper parts of the heaters to remove the air; a thermal deaerator is used in the feed water tank. To evaluate your steam system as a whole, you can take a look at our steam boiler guide and get a free quote for your project.